THE ENERGY INFRASTRUCTURE IS UNDERGOING transformational changes to adapt to accelerated demand growth driven by the adoption of technological innovations such as large loads from data centers and electrification of transportation sectors, policies motivating widespread electrification, and changing weather patterns. To address this challenge, there is an urgent need for tools and information that provide a better understanding of these changing energy demand landscapes and the relationship with the existing and future energy infrastructure. Addressing the challenges at the interface of climate and changing energy demands has been the focus of a collaboration between the New York Power Authority (NYPA) and the University at Albany (UAlbany) Atmospheric Science Research Center.
Key specific motivations for this collaborative effort are policies in place to transform the New York State (NYS) grid to a fully electrified state. At the local scale, New York City (NYC) has set strict decarbonization targets under Local Law 97 (LL97), mandating an 80% reduction in carbon emissions by the year 2050. At the NYS level, the Climate Leadership and Community Protection Act (CLCPA) established a goal of 100% zero-emission electricity by 2040 and 85% carbon reduction by 2050 from 1990 levels. These policies will have deep implications on the energy infrastructure from both increasing demand due to electrification of major sectors (e.g., buildings and transportation) and generation by noncarbon sources (e.g., renewables and nuclear). Additional relevant elements for load modifications are the introduction of large loads such as data centers in the congested grid of the state.
The main activities for the collaborative work include the data provisioning and forecasting of energy demands across NYS from 2020 to 2059 at scales useful to the NYS transmission grid (Figure 1). This required the use of UAlbany’s novel integrated modeling framework that includes an existing high-resolution climate and weather community model connected to the built environment and the energy infrastructures that provide detailed information on future energy demand. Such a modeling framework has been tested before in the context of a large metropolitan area (NYC) and is extended here to the statewide scale for the first time.
Key specific motivations for this collaborative effort are policies in place to transform the New York State (NYS) grid to a fully electrified state. used in this study. The process begins with policy-driven electrification scenarios, followed by high-resolution climate downscaling, building and load modeling, bias correction using observed New York Independent System Operator (NYISO) load data, positive large load modifiers, and further allocation of projected demand from NYISO zones to individual substations. The resulting datasets are then made accessible through an interactive dashboard and structured for integration into power-system simulation and digital-twin (DT) platforms. Using this workflow, we developed scenarios to quantify future energy demands under building and transportation electrification [electric vehicles (EVs)], emerging large loads such as data centers, and a changing climate. This article presents the motivation behind the collaboration,
This collaborative framework is transferable to other jurisdictions facing the combined challenges of grid electrification, load
growth, and climate adaptation. the methodology used to develop the projections, and a synthesis of key results. While demonstrated for NYS, this collaborative framework is transferable to other jurisdictions facing the combined challenges of grid electrification, load growth, and climate adaptation.
Methods
Future Climate Scenarios
The Intergovernmental Panel on Climate Change (IPCC), organized by the United Nations, has built an ensemble of climate models used to forecast the future global climate using global circulation models (GCMs) and socioeconomic conditions. The GCMs represent the physical processes of the Earth system climate, namely land-atmosphere-ocean interactions with the corresponding natural cycles and anthropogenic interventions. The anthropogenic interventions quantify the societal state and how it manifests in physical variables such as emissions that may influence the global energy and mass balance, including carbon emissions. A key role of the IPCC is to prepare comprehensive reports about the scientific, technical, and socioeconomic knowledge of the state of the climate present and future and its impacts and future risks. It convenes the scientific community and shares data and findings in the form of reports. The latest report is the Sixth Assessment Report. The Sixth Assessment includes the Coupled Model Intercomparison Project (CMIP6), which affords a set of climate simulations to evaluate past and future climate change, where long-term simulations are made available for climate responses to changing atmospheric composition and land cover. The CMIP6 is an evolution from the CMIP5, where the concentration feedback of global carbon is accounted for based on a reference state representing no carbon reduction policies in place. In CMIP6, these are referred to as Socio-economic Pathways (SSPs), with a range of policies that will influence the global greenhouse effect in the form of radiation forcing (W/m2).
This joint effort, NYPA-UAlbany, makes use of two scenarios, SSP5-8.5 and SSP2-4.5, to represent a high and moderate emissions scenario consistent with the NYS Energy Research and Development Agency (NYSERDA). Climate downscaling translates coarse spatial resolution global climate models (hundreds of kilometers) into finer-scale projections for a specific region (tens of kilometers). To achieve the necessary resolution for our study of NYS, we downscaled CMIP6 GCM ensembles from the IPCC, typically at 1° spatial resolution (∼100 km), using a refined U.S. Department of Energy GCM ensemble of climate simulations as input to our more localized models. This dataset provides 40 years of historical (1980–2019) and 80 years of future (2020–2099) climate simulations for the continental United States at 12-km spatial resolution. The dataset is referred to as IM3/HyperFACETS Thermodynamic Global Warming (TGW) Simulation Datasets, and it is publicly available. We have further downscaled these data to 4-km resolution for the Northeast and 1.3-km resolution for the NYC metropolitan area using our version of the Weather Research and Forecasting (WRF) model with urbanized physics [e.g., urban WRF (uWRF)]. Figure 2 illustrates this spatial downscaling approach from the continental United States to NYC.
uWRF
In general, WRF is a mesoscale numerical weather prediction system used for weather-related research and forecasting. Meteorological models at the mesoscale (5–100 km) provide the capability to explore regional and local climate and energy questions using a detailed model representation of the atmosphere and the local landscape by computing the conservation equations of mass, momentum, energy, and air humidity at this interface. At the mesoscale, many processes affect how the atmospheric circulation is resolved. This includes the interaction of the land use type and surface characteristics, complex topography, water bodies, and atmospheric aerosols. This also includes the role of urban morphology, which can significantly influence the dynamical state of the environment. The urban area can be characterized by building area coverage, high density of vertical surfaces with varying heights, and surfaces made of engineered materials. These characteristics cause the surface–atmosphere interaction to differ in comparison to the natural environment. This unique surface energy balance tends to cause the urban areas to be warmer, with increases in temperature of up to
These results confirm that the uWRF framework provides a reliable representation of electricity demand in the most densely populated zone of the NYISO system.
15 °F, leading to the urban heat island. When coupled with building effect parameterization and the building energy model (BEP-BEM), the mesoscale model can serve as an appropriate urban-climate modeling framework that has been proven to capture these unique urban heat island effects and also energy demands simultaneously. Most of the previous urban WRF applications have explored extreme heat events in cities, including for NYC.
BEP is a multilayer urban parameterization that models the atmospheric effects caused by urban buildings and includes heat flux adjustments to account for radiation shadowing, reflection, and entrapment within the street canyons. The BEM is coupled with BEP to account for urban heat fluxes caused by heat exchanges between the buildings and the environment. This includes the heat transfer between the walls, floors, and roofs of a building, the solar radiation heat exchange through windows, and the effects of heating, ventilation, and air conditioning (HVAC).
Within this system, the indoor air temperature and indoor air humidity are found by calculating the cooling/heating load needed to maintain comfort levels on a simplified box-type heat budget model that piles up like boxes to consider several floors in a building. This model is driven by the inputs of the WRF model, such as the outdoor air temperature, humidity, and radiation reaching the walls and roof of the building.
The model estimates the sensible and latent heat needed for cooling or heating the indoor air for the floor when a target temperature is set, typically 72 °F for cooling and 68 °F for heating. From this, the electricity demand EC is found by taking into account the system efficiency metrics of the HVAC
The methodology has the potential to analyze multiple events and impacts at particular assets and guide decision making for future infrastructure upgrades.
System used, whether an AC system for summer cooling or an air source heat pump (ASHP) or a gas heating system for winter (eff).The AC and ASHP’s coefficient of performance (COP) typically ranges between two and five and reflects its ability to produce heat per unit of electrical energy consumed. On the other hand, a boiler’s eff , usually between 70% and 90%, represents the proportion of useful heat output to the energy input from fuel combustion. For this study, we assumed that the COP and eff remain constant for each building type (3 and 0.8, respectively). This assumption accommodates the model’s limitation in representing more detailed system dynamics. Nonetheless, the energy demand calculations capture the key factors in system performance, particularly the difference between each heating system type.
This modeling approach makes no distinction between window AC units or central AC systems. The key assumption with this setup is that all heat releases at the top of the building. An aircooled approach is used for the residential buildings, while a water-cooled approach is used for the commercial buildings. It is worth noting that this modeling framework for a large stock of buildings allows for varying the penetration rates of heat pump adoption for building electrification consistent with policies to reach the decarbonization goals by 2050.
Figure 3 shows a visual representation of this entire built-environment-buildings-coupled process. We refer to WRF coupled to BEP+BEM as uWRF. In general, this framework is a simplified version of more detailed single BEMs, such as EnergyPlus™, but they reduce computational costs significantly and are suitable for studies at the city scale or state scale where thousands of buildings are active at the same time. Our team has applied this uWRF system for city-scale energy demands for Beijing, NYC, Los Angeles, and San Juan, Puerto Rico, with very good results when compared with actual energy demand observations. The current work is the first time such a modeling framework has been used for a whole state, such as New York.
To obtain the city-and-state-scale energy loads from BEM outputs, the spatially gridded 1.3-km (in NYC) and 4.4-km (outside NYC) resolution modeled AC consumption (W/m2) is multiplied by the building area fraction and the actual grid spacing area (1.7 or 16 km2), yielding the total building energy demand per grid point. This was then added to the baseline load, a city-wide weatherindependent load derived from NYISO, which represents the nonbuilding associated loads per zone. This methodology for the baseline load ( ), EBaselineand weather component (E∆Wx) can be summarized as EE E Total Baseline = + ∆Wx , where EBaseline is the weather-independent component of the load, and E∆Wx is the weather-dependent component. Prior to combining these components, an artificial intelligence-based bias correction is applied to the weather-dependent HVAC loads derived from the uWRF model outputs, using observed NYISO zonal load data to reduce systematic errors in the modeled energy demand.
The baseline load component is estimated based on NYISO zonal hourly load instances where minimal use of HVAC is expected due to excellent weather conditions. This typically occurs in the shoulder seasons of late spring and early fall. A multiyear analysis of these events per zone results in diurnal cycles of baseline load. Details of this methodology for baseline load have been reported previously by our group.
We modify the future baseline load for all NYISO zones by applying a set of positive and negative modifiers that account for evolving demand drivers between 2020 and 2059, including large loadprojects and decarbonization penetration rates from the transportation sector. Among these, large loadprojects, primarily data centers and manufacturing facilities, represent one of the most significant and rapidly growing demand drivers, contributing an estimated 0.38% annual increase to the baseline. As these facilities come online across NYS, they introduce substantial concentrated loads that can fundamentally reshape demand patterns at both the zone and substation levels. Additional positive modifiers include economic growth and building electrification, while negative modifiers, such as energy efficiency improvements and behind-the-meter solar, partially offset the overall increase. These rates were derived from NYISO’s published annual energy forecasts, yielding a net annual baseline increase of approximately 0.04%. The framework’s ability to incorporate these large load projects directly into the baseline projections allows NYPA to anticipate localized demand surges and assess their implications for transmission planning and infrastructure investment.
This modified baseline is then combined with the bias-corrected HVAC building load estimated by the uWRF model to produce a total zone-level energy demand, as illustrated in the overall framework shown in Figure 2. To translate zone-level energy demand projections into actionable insights at the substation level, a nominal load-based allocation methodology was developed. Each substation’s rated capacity is used to determine its proportional share of the total zone demand so that substations with higher capacity are assigned a correspondingly larger fraction of the zone-level load. This weighting approach distributes the hourly demand time series across all substations within a given zone in a physically consistent manner.
Substation locations provided by NYPA enabled precise geographic assignment of each facility to its corresponding NYISO zone. The resulting substation-level demand profiles give NYPA granular visibility into how energy loads are distributed across individual transmission assets, supporting infrastructure planning and vulnerability assessment under both historical and future climate scenarios.
Future Energy Scenarios
Future energy scenarios for NYS are mostly policy driven. These include the CLCPA (Climate Act) and NYC LL97.
LL97 aspires to decarbonize the largest buildings in the city by 2050, with an interim goal of 40% reduction by 2030.LL97 generally covers, with some exceptions, the following:
✔ buildings that exceed 25,000 gross ft2
✔ two or more buildings on the same tax lot that together exceed 50,000 ft2
✔ two or more buildings owned by a condo association that are governed by the same board of managers and that together exceed 50,000 ft2.
The Climate Act is among the most ambitious climate laws in the nation and requires New York to reduce economy-wide greenhouse gas emissions 40% by 2030 and no less than 85% by 2050 from 1990 levels. This includes all sectors, namely transportation via EVs, and residential and commercial buildings, agriculture, and other sectors.
This set of policies has set forward energy demand projections for the whole state and per NYISO zones. NYISO energy demand projections are well documented in the Gold Book of 2025. A key highlight of these projections is the anticipated increase in winter electricity demand due to the growing adoption of electric space heating technologies, such as heat pump systems (HPSs), particularly in NYC. NYISO projections for new peak demands by 2050 indicate a new winter peak between 50 and 75 GW and summer peaks between 35 and 50 GW, from the current 25 GW, subject to the various penetration rates for electrification of the building and EV sectors. The aggressive NYISO scenario is based on a 100% EV penetration rate by 2050 and 90% for the building sector with a gradient of adoption of different HPSs, whether air source ASHPs or ground-based HPSs.
NYSERDA has conducted independent energy projections based on climate projections (SSPs 245 and SSPs 585) and decarbonization policies. NYSERDA projections coincide with NYISO for summer; however, there is a significant difference in the winter peak for the most aggressive scenarios (75 MW versus 55 MW).
Synthesis of the Scenarios to Quantify Future Energy Demands
Based on IPCC CMIP6 climate projections, NYS and NYC policies, and NYISO and NYSERDA demand projections, the team proposed the following ensemble for future energy demand projections, outlined in Table 1. This ensemble comprises four sets of simulations that take into account two IPCC SSPs consistent with NYSERDA and one decarbonization scenario consistent with both NYISO and NYSERDA. This ensemble has produced a rich dataset of great value to NYPA and a much wider range of stakeholders with invested interest in energy planning and also in climate impacts.
Framework Validation
The evaluation compares modeled hourly demand with observed NYISO loads using root mean square error (RMSE), mean absolute error (MAE), and the coefficient of determination (R2). To facilitate cross-zone NYISO comparisons, RMSE and MAE were normalized by the mean energy demand in each zone [normalized RMSE (NRMSE) or normalized MAE (NMAE)]. The historical period spans 2010 to 2019 for all zones, except for NYISO-D, where the analysis is limited to 2015–2019 due to a documented structural shift in industrial load around 2014. Figure 4 shows the spatial distribution of normalized RMSE across all NYISO zones, demonstrating performance within 10% of the mean load for all zones.
To provide a more detailed assessment of model performance, Table 2 presents annual NRMSE, NMAE, and R2values for NYISO Zone J (NYC) over the period 2010–2019. Zone J is highlighted here given its significance as the largest load center in the NYISO footprint and the particular challenges it poses for demand modeling due to its high population density and weather sensitivity. Across all years, the model maintains an R2above 0.9, with NRMSE values that remain consistent from year to year (below 7%), indicating stable performance without notable degradation over time. Figure 5 further illustrates these results through a time-series comparison of observed and uWRF-modeled hourly loads and a scatter plot of modeled versus observed values, with daily mean overlays for the same period. The time series demonstrates that the model closely tracks the seasonal and diurnal cycles in electricity demand, faithfully reproducing summer peaks and winter troughs. The scatter plot reveals a strong linear correspondence along the 1:1 line, particularly for the dail mean values, though some dispersion is evident at the highest hourly loads, where peak demand events driven by extreme heat are occasionally underestimated. Overall, these results confirm that the uWRF framework provides a reliable representation of electricity demand in the most densely populated zone of the NYISO system
To enable practical use of the extensive climate and energy demand datasets produced by this framework, a web-based interactive dashboard was developed.
Future Load Forecast
The load forecast framework enables variable penetration rates of electrification of buildings and EVs at the grid, zone, and substation levels. To illustrate the demand forecast impacts across scales, the case of a heat wave in 2018 is taken as a reference. Figure 6 illustrates the load demand changes for all zones for the heat wave in July 2018 and the projected demand in a warmer climate and electrified state in July 2058. The same figure illustrates how a substation in lower Manhattan would manage this load, taking into account electrification of buildings and transportation, showing that the capacity of the substation will likely be exceeded in the rated capacity of 98 MW in an electrified future climate (2058). The methodology has the potential to analyze multiple events and impacts at particular assets and guide decision making for future infrastructure upgrades.
Analyzing a five-year historical period (2015–2019) against its future analog (2055–2059) under SSP2-4.5 reveals significant shifts in seasonal peak intensity across the NYC metropolitan area [NYISO Zones I, J, and K, representing the suburbs of Westchester (I) and Long Island (K) and NYC (J)], shown in Figure 7. Building electrification emerges as the dominant driver of winter peak growth, with November–March 95th percentile daily peaks increasing by approximately 20–60% relative to historical conditions even without EVs loads. The effect is most pronounced in Zone J (NYC), where winter peaks rise from roughly 7,000 MW to more than 10,000 MW under the SSP2-4.5 scenario alone. EVs adoption compounds this growth, adding an additional 10–25% to monthly peaks in most months and elevating loads year-round. While summer peaks also increase under future scenarios, the relative growth in winter demand narrows the traditional gap between summer and winter peaks, making winter planning increasingly relevant for grid reliability and infrastructure sizing.
Data Access Portal
To enable practical use of the extensive climate and energy demand datasets produced by this framework, a web-based interactive dashboard was developed. The platform allows users to explore and compare energy demand scenarios across historical and future time horizons, providing visualization of local climate conditions, building HVAC loads, transportation-related demand, baseline consumption, and their combined effects at both the zone and substation levels.
To handle the large volumes of climate and energy data efficiently, the platform relies on a streamlined data processing pipeline that aggregates and preprocesses simulation outputs before they reach the dashboard. Data are organized into spatial and temporal chunks, allowing the system to deliver only the information relevant to the user’s current view rather than loading entire datasets at once. As users interact with the interface through actions such as filtering, zooming, or selecting different time periods, additional data are fetched on demand. This approach ensures fast and responsive visualizations even when working with decades of high-resolution climate and energy projections across all substations in the NYPA system.
The dashboard also incorporates analytical capabilities, such as quantifying changes in peak and average loads across different time periods and climate scenarios. Figure 8 illustrates one such use case, where a cold snap event from February 2016 is compared against its projected counterpart in 2056 under future climate conditions, showing side-by-side weather and load profiles. This type of analysis enables planners and engineers to assess how extreme weather events may evolve and impact energy infrastructure in the coming decades. The platform supports this analysis across all substations within the NYPA system, providing a scalable tool for informed grid planning and resilience assessment.
Integration of Load and Climate Data into Power Grid Simulation Platforms
As referred to in the beginning of this article, one of the key ongoing initiatives at NYPA is the development of a comprehensive DT of the NYS power grid. A foundational component of the DT effort is a full high-fidelity model of the transmission network running on a multiport field-programmable gate array-based orchestrator, which has been used to integrate several commercial simulators and high-performance computing servers. As the field-programmable gate array ensures deterministic data exchange between multiple servers and simulators, the platform supports both real-time and offline simulation of large-scale models and has been successfully tested on the NYS transmission system.
The platform is utilized to run a wide range of studies, including stability analysis of the grid under diverse operating conditions and stress testing of the transmission network under future scenarios such as load growth, interconnection queue expansion, and extreme weather events. The integration of high-resolution climate and load data described here is critical to the DT’s
The integration of the climate and load projections with DTs creates a pathway to move from planning studies to continuous data-driven decision support.
accuracy as it enables dynamic simulation of weather-dependent grid assets, including renewable generation, transmission line ratings, and load behavior. By leveraging both historical and forecasted data, the platform captures temporal and spatial variability in climate conditions, allowing precise modeling of how weather-driven factors influence power flows, asset performance, and system reliability over time. This capability allows operators and planners to evaluate grid resilience under realistic climate scenarios, anticipate risks associated with extreme events, and make informed decisions for long-term planning and operational readiness.
The DT platform requires time-series profiles of climate and load parameters to drive models of renewable energy resources and demand. The load profiles selected in the dashboard, presented in the previous section, are saved in the Zarr format. They are then stored in a large-scale storage cluster managed by an industrial data infrastructure platform designed to collect, store, and manage timeseries data, as illustrated in Figure 9. Zarr is a cloudnative data storage format designed to store large multidimensional datasets such as weather and load data in small and independently accessible chunks. This chunked architecture enables efficient and parallel access to specific subsets of data without loading entire datasets into memory. Its key advantages include scalability for handling terabyte-scale data, fast I/O performance through selective data access, and support for real-time streaming of time-series data. These capabilities make Zarr particularly well suited for DT platforms, where high-resolution data must be continuously accessed and processed to simulate grid behavior accurately.
Specific communication interface adapters have been developed to read these profiles from the storage cluster in configurable fixed-size data chunks and stream them in real time to the simulators and servers that run the DT. The adapters stream data in accordance with the native resolution of the data stored in the database; for example, a signal stored with 1-s time steps is streamed to downstream consumers at a rate of one data point per second. The data received by the DT platform is then parsed and used to update weather parameters supplied to the renewable energy resource models and to adjust the active power consumption of the loads.
In summary, the overall framework of load forecast and power grid interconnection is transformative, presently needed due to the rapidly changing load landscape, and transferable to other jurisdictions under varying policies and power grid configurations. The transferable element of the framework lies in the way it connects climate information, evolving demand drivers, and power-system modeling into a consistent planning workflow. In this study, those demand drivers include weather-sensitive building loads, building and transportation electrification, large load growth, and observed load behavior used for bias correction and calibration. To apply the framework in another jurisdiction, the weathermodel domain, grid topology, observed load data, and policy-driven scenarios would need to be adapted to the local context. For example, EV adoption may advance more rapidly in some regions, while building electrification targets, large load growth, and planning requirements may differ elsewhere. With these location-specific adjustments, the same overall approach can be used to support climate-informed load forecasting and power system planning in other regions. The combination of a load forecast that takes into account variable climate, electrification rates, and large loads at the substation scales with grid topology makes up for unique DTs to enable comprehensive exploration of load-generation transmission/distribution scenarios
The Way Forward
The work presented here represents an important step toward integrating climate-informed load forecasting into utility planning processes. However, significant opportunities remain to further improve both the fidelity of the forecasts and their usefulness for grid operations.
One area of future work is the incorporation of more complex weather scenarios, including prolonged heat waves, extended cold-weather events, and compound events involving multiple weather stressors. These conditions can place sustained stress on both electric demand and transmission assets and are becoming increasingly important in long-term planning studies.
Future development will also focus on better representing emerging demand patterns and customer behavior. This includes the continued growth of EVs, demand response programs, flexible load management strategies, and large new loads such as data centers and advanced manufacturing facilities. Improved representation of these factors will provide a more realistic view of future demand growth and peak loading conditions.
As distributed energy resources continue to expand, additional work will be directed toward incorporating distributed solar generation, battery energy storage systems, and other behind-the-meter resources into the forecasting framework. Understanding how these resources influence local and system-wide demand will become increasingly important for system planning.
On the power system side, the integration of the climate and load projections with DTs creates a pathway to move from planning studies to continuous data-driven decision support. Future work will focus on automating the flow from scenario selection in the dashboard to real-time or faster-thanreal-time simulations on the DT platform, enabling rapid screening of investment options, protection schemes, and operating strategies under different climate and electrification scenarios.
Although this work was developed using New York-specific climate projections, policies, and infrastructure data, the underlying methodology is broadly applicable. With appropriate regional inputs, the framework can be adapted to support load forecasting, infrastructure planning, and climateresilience studies in other jurisdictions facing similar challenges associated with electrification, large load growth, and changing climate projections.
For Further Reading
L. E. Ortiz, J. E. Gonzalez, E. Gutierrez, and M. Arend, “Forecasting building energy demands with a coupled weather-building energy model in a dense urban environment,” ASME J. Sol. Energy Eng., vol. 139, no. 1, 2017, Art. no. 011002, doi: 10.1115/1.4034909.
D. Jones et al., “Continental United States climate projections based on thermodynamic modification of historical weather,” Sci. Data, vol. 10, no. 1, 2023, Art. no. 664, doi: 10.1038/s41597-023-02485-5.
Core Writing Team, H. Lee, and J. Romero, “Climate change 2023: Synthesis report, contribution of working groups I, II and III to the sixth assessment report of the intergovernmental panel on climate change, IPCC, Geneva, Switzerland, 2023. [Online]. Available: https://www.ipcc.ch/report/ar6/syr/downloads/report/IPCC_AR6_SYR_FullVolume.pdf
F. Salamanca, A. Krpo, A. Martilli, and A. Clappier, “A new building energy model coupled with an urban canopy parameterization for urban climate simulations—Part I. Formulation, verification, and sensitivity analysis of the model,” Theor. Appl. Climatol., vol. 99, nos. 3–4, pp. 331–344, 2010, doi: 10.1007/s00704-009-0142-9
New York State Energy Research and Development Authority (NYSERDA), “Impacts of climate change on the New York energy system,” Energy Environ. Econ., New York, NY, USA, NYSERDA Rep. no. 23-30, 2023.
J. P. Montoya-Rincon and J. E. Gonzalez-Cruz, “Artificial intelligence-driven cooling load forecasts in dense urban environments,” ASME. J. Eng. Sustain. Bldgs. Cities, vol. 7, no. 2, 2026, Art. no. 024502, doi: 10.1115/1.4071827.
K. P. Sookdar et al., “The peak energy load management system: A case study in Montreal,” ASME. J. Eng. Sustain. Bldgs. Cities, vol. 7, no. 3, 2026, Art. no. 031002, doi: 10.1115/1.4071208.
Biographies
Juan Pablo Montoya-Rincon is with the University at Albany, Atmospheric Sciences Research Center, Albany, NY 12222 USA.
Harold Gamarro is with the University at Albany, Atmospheric Sciences Research Center, Albany, NY 12222 USA.
Kaiden Sookdar is with the University at Albany, Atmospheric Sciences Research Center, Albany, NY 12222 USA.
Nour Elgalad is with the University at Albany, Atmospheric Sciences Research Center, Albany, NY 12222 USA.
Varun Paul Reddy Gade is with the University at Albany, Atmospheric Sciences Research Center, Albany, NY 12222 USA.
Jan Woodcock is with the University at Albany, Atmospheric Sciences Research Center, Albany, NY 12222 USA.
Jorge E. González-Cruz is with the University at Albany, Atmospheric Sciences Research Center, Albany, NY 12222 USA.
Tung Lam Nguyen is with the New York Power Authority, Albany, NY 12203 USA.
Rahul Kadavil is with the New York Power Authority, Albany, NY 12203 USA.
Hossein Hooshyar is with the New York Power Authority, Albany, NY 12203 USA